ONAF (Oil Natural Air Forced) — Transformer Glossary

    Cooling method where oil circulates by natural convection but fans force air over the radiators, increasing cooling capacity by 25–40%.

    Backcooling

    ONAF (Oil Natural Air Forced)

    Cooling method where oil circulates by natural convection but fans force air over the radiators, increasing cooling capacity by 25–40%.

    ONAF fans are typically thermostatically controlled, activating when oil temperature exceeds a setpoint (usually 65–75°C). This provides automatic load management: the transformer operates silently in ONAN at base load and activates fans only during peak demand. Dual-rated transformers (e.g., 80/100 MVA ONAN/ONAF) are common in utility applications where load varies significantly between day and night.

    Ready to Specify

    Get a Quote Tailored to This Specification

    Send us your application context — we'll come back with a sized solution, certified to IEC, IEEE/ANSI or UL, and a delivery slot from our Dubai factory.

    Talk to Engineering

    Can't Find What You Need?

    Our engineering team is happy to answer technical questions and provide custom documentation.