Power Factor (PF) — Transformer Glossary
The ratio of real power (kW) to apparent power (kVA) in an AC circuit. Ranges from 0 to 1, where 1 represents a purely resistive load.
Power Factor (PF)
The ratio of real power (kW) to apparent power (kVA) in an AC circuit. Ranges from 0 to 1, where 1 represents a purely resistive load.
Power factor directly impacts transformer sizing. A load drawing 800 kW at 0.8 power factor requires a 1,000 kVA transformer, but the same 800 kW at 0.95 power factor needs only 842 kVA. Low power factor causes: increased I²R losses in windings, reduced usable capacity, and higher electricity bills (utilities penalise PF below 0.9). Power factor correction using capacitor banks or active filters can reduce the required transformer rating and improve system efficiency.