Earthing (Grounding) Transformers — view 1 of 1
    Neutral Grounding
    5MVA
    Max Rating
    36kV
    Voltage Class
    10s
    Short-Time Rating
    30yr
    Design Life
    Neutral Grounding · Zigzag / Star-Delta · Up to 36 kV

    Earthing (Grounding) Transformers

    Earthing transformers providing an artificial neutral point for unearthed or delta-connected MV systems — enabling reliable ground-fault detection, controlled fault clearance, and protection coordination in industrial and renewable networks.

    IEC 60076-6
    IEEE C57.12
    IEEE C57.32
    IEEE C62.92
    ISO 9001
    Rating
    50 kVA – 5 MVA
    Voltage Class
    Up to 36 kV
    Winding Configuration
    Zigzag / Star-Delta
    Standards
    IEC 60076-6 / IEEE C57
    Cooling
    ONAN / KNAN
    Short-Time Rating
    10 s typical
    Type Tested
    Warranty
    Global

    Engineering Features

    Zigzag or Star-Delta Winding

    Standard zigzag configuration for compact footprint, or star-delta with separate auxiliary winding when station service is required.

    Technical Data

    ParameterRange / Value
    Rated Power50 kVA – 5 MVA (continuous equivalent)
    System VoltageUp to 36 kV
    Frequency50 / 60 Hz
    Winding TypeZigzag (Z) / Star-Delta (YNd)
    Short-Time CurrentProject-specific (typ. 400–4000 A for 10 s)
    CoolingONAN / KNAN
    Insulation ClassBIL 75 / 125 / 170 kV per voltage class
    Auxiliary WindingOptional 230/400 V
    StandardsIEC 60076-6 / IEEE C57.32 / IEEE C62.92
    Design Life30+ years

    Standard range parameters — custom specifications available on request.

    UK Compliance & Trust Signals

    ENATS 35-1

    DNO-approved distribution transformer specification

    ENATS 35-2

    UK secondary substation transformer standard

    G99 Compliant

    Engineering Recommendation G99 grid interface

    BS EN 60076

    British Standard for power transformers

    KEMA Certified

    Independent short-circuit witness testing

    EcoDesign Tier 2

    EU 548/2014 efficiency compliance

    Regional Overview

    Zigzag and star-delta earthing (grounding) transformers for UK utility, industrial and renewable service. 50 kVA to 5 MVA at up to 36 kV per BS EN 60076-6, providing an artificial neutral on ungrounded delta or IT systems. Used with neutral-earthing resistors (NER) and reactors for fault-current limitation in DNO secondary distribution, renewable plants and industrial process power.

    Regional Reference Projects

    UK Renewable IPP Earthing · Solar & Wind Farms

    UK DNO Distribution Network Neutral Grounding

    Industrial Process Plants · Earthing for IT Systems

    Network Rail Traction Substation Earthing

    BESS Site Neutral-Grounding Transformers

    UK Petrochemical & Process Plants · Earthing Service

    Applications

    Where Earthing (Grounding) Transformers Excel.

    01
    01

    UK Renewable IPP Earthing

    Zigzag earthing transformers providing artificial neutral on UK solar and wind farm collection systems for G99 grid-code compliance.

    02
    02

    DNO Distribution Network Grounding

    BS EN 60076-6 zigzag transformers for UKPN, NIE, SP Energy and Northern Powergrid neutral-grounding on ungrounded delta systems.

    03
    03

    Industrial IT-System Earthing

    Star-delta earthing transformers for UK industrial process plants requiring artificial neutral on IT or ungrounded systems.

    04
    04

    BESS Site Neutral-Grounding

    Earthing transformers for UK Battery Energy Storage System sites — paired with NER for fault-current limitation and grid compliance.

    FAQ

    Frequently Asked Questions

    Ready to Specify Earthing Transformers?

    Share your technical requirements and our engineering team will provide a detailed proposal with guaranteed performance parameters.