Temperature Rise — Transformer Glossary

    The increase in winding and oil temperature above ambient when the transformer operates at rated load. A key specification for transformer longevity.

    Backmechanical

    Temperature Rise

    The increase in winding and oil temperature above ambient when the transformer operates at rated load. A key specification for transformer longevity.

    IEC 60076 specifies: top oil temperature rise ≤ 60K, average winding rise ≤ 65K (for Class A insulation at 40°C ambient). IEEE C57 specifies: top oil ≤ 65°C, average winding ≤ 65°C above ambient. For every 6–8°C above rated hot-spot temperature, insulation life is halved (Arrhenius rule). Tropical regions (55°C ambient) require derating or enhanced cooling to maintain insulation life.