Buchholz Relay — Transformer Glossary

    A gas-actuated protective relay installed in the pipe between the main tank and conservator of oil-filled transformers. Detects gas accumulation from internal faults.

    Backprotection

    Buchholz Relay

    A gas-actuated protective relay installed in the pipe between the main tank and conservator of oil-filled transformers. Detects gas accumulation from internal faults.

    The Buchholz relay provides two stages of protection: (1) Alarm stage — triggered by slow gas accumulation from minor faults (partial discharge, hot spots). The relay collects gas and activates an alarm contact when the gas volume exceeds a threshold. (2) Trip stage — triggered by rapid oil surge caused by severe internal faults (arc, short circuit). The oil displacement activates a trip contact that disconnects the transformer. The collected gas can be analysed to identify the fault type (DGA).